| Brand | Rw Energy |
| Model NO. | High‑Performance Static Var Generator (SVG) |
| Rated voltage | 380V |
| Rated frequency | 50Hz |
| Series | RWSVG |
The RWSVG Static Var Generator is designed to provide real-time reactive power compensation through advanced self-commutated bridge technology. By connecting the bridge circuit in parallel with the power grid through a reactor, the device precisely regulates the phase angle and amplitude of the AC output voltage, or directly controls the AC-side output current. This enables the SVG to generate the required capacitive or inductive reactive current, ensuring fast, accurate, and stable dynamic reactive power compensation.
The RWSVG effectively improves system power factor, stabilizes voltage, and reduces power losses caused by reactive fluctuations. It also enhances power quality by mitigating issues such as voltage flicker, current distortion, and unbalanced loads. With rapid response and high precision, the RWSVG provides a reliable solution for modern industrial networks facing dynamic loads and stringent power quality requirements.
Provides fast and continuous reactive power compensation to maintain stable system voltage.
Improves power factor and reduces system losses by supplying inductive or capacitive reactive current in real time.
Mitigates voltage fluctuations, current distortion, and load imbalance caused by nonlinear or impact loads.
Uses full-digital control with high sampling accuracy, ensuring stable operation under varying grid conditions.
Offers rapid dynamic response, enabling precise real-time compensation without switching transients or inrush currents.
Supports modular parallel configuration to increase overall compensation capacity.
Integrates comprehensive protections including overvoltage, undervoltage, overcurrent, overload, overheating, short circuit, and communication failure.
Provides detailed monitoring and data logging for voltage, current, power factor, reactive power, harmonics, frequency, and device operating status.
Designed for stable long-term operation with high reliability and minimal maintenance requirements.
Industrial lifting equipment, cranes, and heavy-duty hoisting systems with typical impact loads requiring stable voltage and improved power factor.
Power distribution systems supplying variable-speed drives, welding machines, compressors, pumps, and large impact loads.
Mining, petroleum, drilling, and construction machinery with rapidly changing load demands or severe reactive power fluctuations.
Manufacturing facilities with large-scale automation equipment, PLC systems, CNC machines, and precision electronic devices sensitive to voltage variations.
Data centers and communication stations requiring stable reactive power support and improved power quality.
Commercial buildings, hospitals, laboratories, and public facilities with complex loads causing voltage drop, imbalance, or reactive instability.
Any distribution network where rapid dynamic reactive compensation is needed to improve efficiency, reduce energy loss, and enhance equipment lifetime.
Rated Voltage: 380V (allowable fluctuation range –40% to +20%)
Rated Frequency: 50Hz ±2Hz
Available Capacities: 50kvar, 75kvar, 100kvar, 200kvar (parallel expansion supported)
Compensation Mode: Inductive and capacitive continuous dynamic compensation
Overall Efficiency: ≥97%
Switching Frequency: Approx. 20kHz
CT Requirements: 3 × CT, accuracy class 0.5 or above, secondary current 5A
Response Time (Current Loop): 40μs
Full Compensation Time: 10ms
Harmonic Handling: Capable of suppressing 3× line current
Overvoltage, undervoltage, overcurrent, overload, overheating
IGBT overtemperature, fan failure, device internal fault
Short-circuit and DC bus overvoltage protection
THD-related protection for load current and system stability
Display & Records:
Real-time current, voltage, power factor, THD values
Load current waveform and three-phase voltage waveform
IGBT temperature and internal status
Operating mode, event logs, and system alarms
Communication Interface: RS485 / Ethernet
Protocol: Modbus
Operating Temperature: –10°C to +45°C
Storage Temperature: –20°C to +60°C
Relative Humidity: ≤95% (non-condensing)
Altitude: ≤2000m (higher altitudes require derating)
Protection Grade: IP20
Cooling Method: Intelligent forced air cooling
Wall-mounted, rack-mounted, or integrated cabinet configuration
Dimensions: Customized according to model selection