Leveraging our core product strengths,we offer three key solutions to global clients:First,Smart Grid Optimization Solutions,which utilize recloser controllers and distribution automation systems to enable rapid fault location and automatic restoration, enhancing power supply reliability. Second, Industrial/Residential Energy Storage Solutions, tailored to diverse load demands, helping clients achieve peak shaving,backup power assurance,and energy cost control.Third,EV Charging Network Solutions,providing AC/DC charger selection, network design, and O&M services, compatible with regional standards like North America's NACS and Europe's CCS2. These solutions have been successfully deployed in factories,office buildings,residential communities,and public transport,effectively addressing customer pain points in energy utilization,power stability,and charging convenience.

Distributed Fault Precise Localization System Solution for Transmission Lines


One-sentence conclusion

This solution deploys dual-mode distributed fault location terminals—both contact-based and non-contact-based—for transmission lines above 35 kV, with intervals ranging from 5 to 30 km. It achieves a fault location accuracy of ≤ ±100 m, a segment-level positioning reliability of ≥ 99%, and an identification accuracy for lightning-induced versus non-lightning-induced faults exceeding 95%. As a result, fault patrol time is reduced from hours to minutes.

Distributed Fault Precise Localization System Solution for Transmission Lines

I. Industry Pain Points

  1. Transmission lines are long and span numerous sections; after a fault occurs, manual line inspections can take anywhere from several hours to several days, wasting valuable repair windows.
  2. Lightning strikes, external damage, and wildfires can trigger transient faults; traditional steady-state detection methods are unable to capture traveling-wave transient signals.
  3. The causes of lightning strikes, non-lightning strikes, bypass strikes, and back strikes are intertwined, making it difficult to match the appropriate mitigation strategies precisely.

II. Solution Architecture

Distributed fault location terminal (installed on poles/towers and conductors) + master station system (fault analysis and location software + application/data server) + mobile handheld terminal. It supports both contact-based (traveling-wave current measurement) and non-contact (electric field voltage measurement) modes, allowing for mixed deployment within the same network and flexible blind-spot coverage.

  •  Contact-type: Traveling-wave sensor bandwidth 1 kHz to 2 MHz, single-wire fault current range 10 A to 5000 A, traveling-wave recording duration 500 μs;
  •  Non-contact: Traveling-wave voltage frequency response: 30 Hz to 1 MHz; sampling rate > 1 MHz; continuous recording duration > 1000 μs; voltage linearity: 10 V to 10,000 V (±10% ± 10 V, reference electric field: 10,000 V/m).
  •  The terminals are all installed in a non-series bypass configuration, and single-point failures do not affect the operation of the primary equipment or the main circuit.

III. Core Technical Indicators

Indicator

Contact-based

Non-contact

Applicable Voltage

35kV and above

35kV and above

Positioning error

≤±100m

≤±100m

Interval positioning reliability

≥99%

≥99%

Lightning strike identification accuracy

>95% (lightning/non-lightning, side flash/counterstrike)

>95% (lightning/non-lightning, side flash/counterstrike)

Time reference

BDS ≤ 0.03 μs

BDS ≤ 0.03 μs

Traveling-wave bandwidth/sampling

1kHz~2MHz

Voltage: 30 Hz to 1 MHz; Sampling rate > 1 MHz

Fault Range

Current: 10A ~ 5000A

Voltage: 10V~10,000V

Recording duration

500microseconds

>1000 μs

Protection/Material

IP67 / Aluminum die-cast <6kg

Pole and tower installation—waterproof, moisture-proof, and corrosion-resistant.

Environmental adaptation

-40~+70℃; altitude ≤5000m; gusts ≤45m/s; GB 50545 heavy ice zone

-40~+70℃; altitude ≤5000m; gusts ≤45m/s; GB 50545 heavy ice zone

IV. Deployment Recommendations

  1. Deployment: The spacing between adjacent monitoring points should be 5–30 km. Monitoring points must be installed at transmission-line towers on the power supply side, and the density of monitoring points should be increased along the middle sections of long transmission lines.
  2. Form selection: In areas with frequent lightning strikes, prioritize contact-based sensors (with current ranges covering lightning currents); in sections with restricted access, supplement with non-contact sensors to fill coverage gaps.
  3. Communication Security: Communication with the master station supports VPN/encryption and is configured in accordance with power secondary security requirements.
  4. Acceptance: The positioning error shall be verified by actual line testing (non-contact traveling-wave voltage measurement segment error ±10%).).

V. Application Value

Operations and Maintenance Phase

Traditional model

After deploying this solution

Fault Detection

Manual Inspection/Steady-State Detection

Traveling-wave transient detection, 24-hour online

Fault Localization

Line patrol segment by segment, from hourly to daily levels.

≤±100m, minute-level locking

Cause Determination

On-site experience

Lightning strike vs. non-lightning strike >95% identification

Data Management

Decentralized record

Centralized traceability, VPN encryption

Reference Projects

  • 88 Units 35kV PV Recloser Controllers Colombia
    Executive Technical SummaryDeployment Scope: 88 units of RWK-352HBV intelligent 35 kV recloser controllers customized for utility-scale solar photovoltaic (PV) interconnection.Grid Operator &amp; Market Framework: Engineered strictly in accordance with Colombian national interconnection standards regulated by grid market operator XM S.A. E.S.P..Protection &amp; Renewable Standards: Certified compliant with IEEE 1547:2018 (interconnection of distributed energy resources) and IEEE C37.60 / IEC 602
  • 420 Units of 11 kV Automatic Reclosers for Dhaka Grid Upgrade
    Executive Technical SummaryProject Scale &amp; Apparatus: 420 units of 11 kV pole-mounted intelligent automatic circuit reclosers (ACR) engineered with vacuum interrupters (VI) and single-coil permanent magnetic actuators.Utility Client &amp; Jurisdiction: Manufactured by RW Energy and supplied through authorized in-country engineering partners and EPC distributors for deployment across primary feeder loops under the authority of the Bangladesh Power Development Board (BPDB).Engineering &amp; Cl
  • RW Energy Multi Country SMS Based Auto Recloser Controller Case Study
    Breaking the communication bottlenecks in remote areas worldwide, this solution takes SMS communication as its core innovation and develops recloser controllers adaptable to multiple countries and diverse climates. Free from reliance on 4G networks, it enables rapid fault early warning and remote operation &amp; maintenance management, helping various regions resolve distribution network operation challenges in remote areas and inject intelligent momentum into global rural power grid upgrading.0
  • RW Energy Xinjiang Bazhou Large-scale Data Center 6 kV Industrial Grid Intelligent Power Distribution Upgrade Case Study
    Focusing on the high-reliability power supply demands of data centers, this project upgrades the 6kV industrial intelligent power distribution system. It enhances anti-sandstorm and wide-temperature environmental adaptability, integrates rapid protection and remote intelligent operation and maintenance technologies, stably supports high-density computing loads, and empowers the intelligent transformation of power grids in western computing hubs.01 Project Overview1.1Project BackgroundBayingolin
  • Angola Dadi Energy Storage 35 kV Power Quality Improvement success story
    The Angola Dadi Energy Storage power quality improvement project is a 35 kV power quality retrofit implemented on an existing energy storage plant. On-site nonlinear, high-harmonic loads such as inverters — power conversion systems (PCS) — are densely concentrated, a typical harmonic-source-intensive scenario in which harmonic pollution seriously hampers production efficiency and product quality.An H5+H7 filter compensation bank with a total capacity of 7500 kvar was provided to deliver harmonic
  • Kenya 11kV RMU SCADA Retrofit Project
    Executive Technical SummaryProject Scope &amp; Asset Retrofit: Non-invasive automation and telemetry upgrade for 11 kV Ring Main Units (RMUs) operating on the urban distribution network.Utility Client &amp; Operator: Engineered for integration with the national distribution monitoring center of the Kenya Power and Lighting Company (KPLC).Telecontrol Standards: Implemented dual-protocol telemetry via IEC 60870-5-104 over cellular APN and conformance-verified profiles from the DNP3 Users Group.Ope
  • Abidjan 35kV Substation High Voltage Reactive Power Compensation Project: A Successful Case Study
    Executive Technical SummaryProject Scale &amp; Apparatus: Turnkey delivery of four sets of RWTBBX-35-2500 high-voltage outdoor shunt capacitor compensation systems (total capacity: 10,000 kvar).Utility Client &amp; Regional Grid: Commissioned across key 35 kV urban substations under Compagnie Ivoirienne d'Electricité (CI-Energies) and interconnecting with the West African Power Pool (WAPP).International Engineering Standards: Type-tested per IEC 60871-1:2014 and IEEE 519; verified for internal a
Leave your contact information to receive the full technical documentation and a free consultation from our engineers. Get the Solution Guide
Recent Solutions
Send inquiry
+86
Click to upload file
Download
Experts Electrical is dedicated to serving the personnel in the global power industry.
Join Experts Electrical, not only can you discover power equipment and power knowledge, but also canhnd like - minded friends!
App Store
Download
Get the IEE Business Application
Use the IEE-Business app to find equipment, obtain solutions, connect with experts, and participate in industry collaboration anytime, anywhere—fully supporting the development of your power projects and business.
Chat
Manager
WhatsApp
WhatsApp