占位边距

Products

Integrate the full range of core products, covering energy storage, charging piles, power protection, and other fields, providing detailed specifications and technical parameters

400V/690V/1140V/1380V 160kW~2800k Low Voltage Engineered Frequency Converter
  • 400V/690V/1140V/1380V 160kW~2800k Low Voltage Engineered Frequency Converter
  • 400V/690V/1140V/1380V 160kW~2800k Low Voltage Engineered Frequency Converter
Key attributes
Brand Rw Energy
Model NO. 400V/690V/1140V/1380V 160kW~2800k Low Voltage Engineered Frequency Converter
Rated frequency 50/60Hz
Series HD
Product descriptions from the supplier
Description

Overview

400V, 690V, 1140V, 1380V/160kW~2800kW, and the maximum power of the parallel machine can reach 22400kW

Performance characteristics

Engineered reliability design

  • High redundancy of control system and power system

  • Water-cooled heat dissipation design, low noise and better heat dissipation

  • Optical fiber connection, stronger anti-interference ability

"Blocked" design

  • Modular components, all frontal maintenance

  • No special tools required, simple and convenient maintenance

  • Intelligent fault diagnosis system for quick positioning

Highly adaptable design

  •  Strong grid adaptability, support wide range input of the grid

  • Support single-axis and multi-axis transmission

  • Equipped with unit and unit cabinet series products

  • Support 3 different rectification methods

  • Support a variety of communication protocols and encoder modules

Excellent control

  • Adapted to asynchronous motors and permanent magnet synchronous motors

  • Two-quadrant and four-quadrant rectification schemes

  • Rectification, inverter parallel and parallel current sharing technology

  • OLVC and CLVC control online automatic switching technology

  • Master-slave synchronous control technology

  • Load balancing control technology

Communication Protocols & Smart Software

  • Support multiple communication protocols (Profibus DP, CANopen, Profinet IO, Modbus RTU, Modbus TCP, EtherCAT, EtherNet, ControlNet and DeviceNet)

  • Provide fast debugging tool hopeInsight to realize online parameter setting, status monitoring, intelligent fault recording and fault diagnosis, etc

Main parameters

project

Specifications and technical data

Basic rectification

Input voltage

4:380V~480V,6:500V~690V

Input frequency

(50Hz/60Hz)±6%

Output voltage

Input Voltage*1.32 (Full Load Condition)

Overload capacity

Relative base load current IH_DC allows 150% overload for 60s with a maximum current Imax_DC overload 5s, load cycle 300s

Efficiency

≥99%

Protection function

Overheating protection, soft rise protection, interlock protection, etc

Intelligent rectification

Input voltage

4:380V~480V,6:500V~690V

Input frequency

47~63Hz

Output voltage

Input Voltage*1.3 (Full Load Condition)

Overload capacity

Relative base load current IH_DC allows 150% overload for 60s with a maximum current Imax_DC overload 5s, load cycle 300s

Efficiency

≥98.5%

Protection function

Overheat protection, overcurrent protection, IGBT pass-through protection, etc

PWM rectification

Input voltage

4:380V~480V,6:500V~690V,9:1140V,A:1380V

Input frequency

47~63Hz

Output voltage

Input Voltage*1.5 (Rated Condition)

Overload capacity

Relative base load current IH_DC allows 150% overload for 60s with a maximum current Imax_DC overload 5s, load cycle 300s

Efficiency

≥98% (including LCL filter unit)

Factor

Adjustable (factory set to 1)

Protection function

Over-temperature protection, over-current protection, overload protection, IGBT pass-through protection, etc

Inverse

Rated input voltage

4:410Vdc~780Vdc,6:550Vdc~1100Vdc,9:1488Vdc~2200Vdc

A:1488Vdc~2200Vdc

Output voltage

0~Rectifier AC input voltage

Output frequency

0~500Hz

speed regulation range

V/F:1:50  OLVC:1:200  CLVC:1:1000

Steady speed accuracy

OLVC:0.2% ; CLVC:0.01%

Pulsating speed

OLVC:0.2%; CLVC:0.1%

Start torque

OLVC:150%(0.5Hz) ; CLVC:200%(0Hz)

Torque control

V/F: Not supported; OLVC: Support ; CLVC: Yes

Torque accuracy

OLVC:5% ; CLVC:5%

Torque response time

OLVC:5ms ; CLVC:5ms

RPM response time

OLVC:100ms; CLVC:100ms

Dynamic drop equivalent

OLVC:0.5%*s; CLVC:0.3%*s

environmental conditions

temperature

-15°C~+40°C is not degraded, and +40°C~+55°C is degraded

humidity

5%~95% non-condensation

elevation

≤ 4000m, 2000m~4000m reduced use

Mechanical data

Anti-vibration performance

Complies with IEC 60721-3-3:2002

Protection level

IP00 / IP20 / IP40

Safety level

Meets UL 508C-2004

Cooling method

Cold wind, cold water

Related Products
Related Solutions
Inquiry
Download
Experts Electrical is dedicated to serving the personnel in the global power industry.
Join Experts Electrical, not only can you discover power equipment and power knowledge, but also canhnd like - minded friends!
App Store
Download
Get the IEE Business Application
Use the IEE-Business app to find equipment, obtain solutions, connect with experts, and participate in industry collaboration anytime, anywhere—fully supporting the development of your power projects and business.
Email
E-mail
Chat
Manager
IEE Business
Source professional electrical partners, experts, and explore smart grid & energy solutions.