占位边距
The collection features typical success cases of the company across multiple regions and industries worldwide, covering three core business areas: including a commercial and industrial energy storage system project at a factory in Europe (achieving a 30% reduction in electricity costs), an EV charging network project for a community in North America (compatible with the NACS standard, meeting the charging needs of 500+ parking spaces), and a smart grid optimization project in a region of Asia-Pacific (reducing fault recovery time by 80% through recloser controllers and distribution automation systems), among others.

12 Units of LSVR 90 0.4 4 for Voltage Regulation in Licheng Shanxi


1. Project Background & Challenges

1.1 Project Background

Certain rural distribution areas in Licheng County, Changzhi City, Shanxi Province, faced typical "end-of-line voltage quality" issues. With the rapid growth of rural electricity loads and the implementation of distributed photovoltaic (PV) policies, the existing distribution infrastructure faced dual pressures:

  • Heavy Load Low Voltage: Due to excessively long power supply radii and small conductor cross-sections, the terminal voltage at consumer premises dropped as low as 200V during peak hours, failing to meet national standards and preventing household appliances from starting.

12 Units of LSVR 90 0.4 4 for Voltage Regulation in Licheng Shanxi

  • PV Overvoltage: During peak PV generation periods with low local demand, reverse power flow caused voltage spikes at access points. This led to frequent tripping of PV inverters, affecting residents' generation revenue.

1.2 Objectives

The power supply company required a low-voltage regulation solution capable of automatic, rapid response and bi-directional adjustment to stabilize terminal voltage within the national standard range (220V ±7%) without large-scale line reconstruction.


2. Technical Solution & Parameters

For the complex conditions of this area, 12 units of LSVR-90-0.4/4 low-voltage automatic voltage regulators were selected. The equipment is strictly designed in accordance with IEC 60076-1:2011 and relevant GB standards. The equipment utilizes series compensation principles, achieving precise voltage adjustment by automatically switching transformer taps.

2.1 Core Technical Parameters

The specific configuration for this project is as follows:

Parameter

Technical Specifications / Performance

Model

LSVR-90-0.4/4

Phases

Three-phase

Rated Voltage

380V

Rated Capacity

90kVA

Adjustment Taps

5 Taps

Adjustment Range

±20% (Meets extreme low voltage compensation and PV high voltage suppression)

Regulation Mode

Individual Phase Regulation (Effectively solves voltage deviation caused by unbalanced loads)

Response Time

≤ 100s (Controller sampling frequency and logic support automatic delay adjustment based on deviation—larger deviation leads to faster action)

Total Loss

≤ 0.5%

Bypass Operation

Automatic bypass function (Switches during faults or when voltage is qualified; ensures no power interruption)

Cooling Mode

Natural cooling + Forced air cooling

Connection

Series Connection

Installation

Outdoor Pole-mounted Installation

2.2 Drawings

The LSVR Low-Voltage Automatic Voltage Regulator is mainly composed of a compensation transformer, an intelligent regulation switch, a control system and auxiliary systems. Its wiring schematic diagram is shown as follows:

12 Units of LSVR 90 0.4 4 for Voltage Regulation in Licheng Shanxi

3. Manufacturing & Craftsmanship

3.1 Core Component Selection

  • Autotransformer: Adopts S13 or higher energy efficiency core design concepts, using high-permeability oriented silicon steel sheets to ensure a total loss of ≤ 0.5%, significantly enhancing long-term economic operation.
  • Intelligent Controller: Integrated microprocessor monitors three-phase voltage in real-time, controlling the on-load tap changer based on logic judgment.
  • Protection Design: Tailored for Shanxi's large seasonal temperature variations and dusty environment, the enclosure uses high-corrosion-resistant materials with a protection rating of IP54. The cooling fan inlet is equipped with special dust filters to prevent internal temperature rises caused by fine dust accumulation.

12 Units of LSVR 90 0.4 4 for Voltage Regulation in Licheng Shanxi

4. Testing & Verification

All 12 units underwent rigorous Routine Tests before leaving the factory:

  • Mechanical Operation Test: Verified the accuracy and stability of the 5-tap changer under continuous operation.
  • Regulation Logic Verification: Simulated input voltages from 160V to 260V to verify precise triggering of step-up or step-down actions.
  • Temperature Rise & Insulation Test: Ensured thermal stability and insulation reliability under high load conditions.
  • Automatic Bypass Test: Simulated control power failure to verify the bypass switch's capability to switch within 100ms-200ms, ensuring no sustained power interruption for users.

5. Installation & Summary

5.1 Implementation

The equipment was Pole-mounted, installed directly at the end of the distribution zone or at the start of branches with severe voltage fluctuations. This eliminated the need for additional land acquisition, shortened construction cycles, and reduced overall project costs.

12 Units of LSVR 90 0.4 4 for Voltage Regulation in Licheng Shanxi

5.2 Results

  • Significant Improvement in Voltage Quality:Since commissioning, the terminal voltage—which previously dropped below 200 V—has been stably compensated to over 200 V, achieving full compliance with national grid standards.
  • PV Overvoltage Suppression: During midday PV generation peaks, the equipment automatically entered step-down mode, preventing inverter trips caused by overvoltage.
  • Load Balancing: The individual phase regulation function mitigated voltage differences caused by single-phase load imbalances, extending the lifespan of the distribution transformer.
12 Units of LSVR 90 0.4 4 for Voltage Regulation in Licheng Shanxi

5.3 Conclusion

The LSVR-90-0.4/4 is an economical and efficient tool for solving rural power grid voltage issues. Through this deployment, the Licheng Power Supply Company resolved long-standing terminal power quality issues with minimal investment. This effectively improved local residents' electricity satisfaction.


6. Lifecycle & Service

  • Intelligent Monitoring: Supports remote communication interfaces, enabling integration with the power grid monitoring system for real-time status awareness.
  • Maintenance-Free Design: Core switches have a long service life, requiring no manual attendance during daily operation.
  • Technical Support: We provide 24/7 technical consultation and on-site guidance to ensure long-term stable operation.
Leave your contact information to receive the full technical white paper, equipment list, and energy efficiency report for this case. Request Reference Materials
Recent Success Reference
Send inquiry
+86
Click to upload file
Download
Experts Electrical is dedicated to serving the personnel in the global power industry.
Join Experts Electrical, not only can you discover power equipment and power knowledge, but also canhnd like - minded friends!
App Store
Download
Get the IEE Business Application
Use the IEE-Business app to find equipment, obtain solutions, connect with experts, and participate in industry collaboration anytime, anywhere—fully supporting the development of your power projects and business.
Email
E-mail
Chat
Manager
WhatsApp
WhatsApp